The requirement in this network is that the ground fault protection shall have
sensitivity so that ground faults with resistance up to 3 000 Ω shall be detected and
cleared.
The residual voltage at 3 000 Ω works out as:
0
138000
3
0 52 79674 41431
3
3 3000
1
1
9561
Phase
o
f
V
/
V
.
V
R
Z
=
=
=
×
=
×
×
+
+
GUID-788DE8BD-9D07-463D-90D8-BAE663628155 V1 EN
(Equation 31)
This corresponds to 52 % of residual voltage at non-resistive (solid) phase-to-ground
fault.
The active current works out as:
0
0 52 25 13
j,active
Rn
Phase
V
I
I
.
A
V
=
×
=
×
=
GUID-1CA3ABED-3D49-477D-B0D2-9CCEEB24684F V1 EN
(Equation 32)
This corresponds to 52 % of the neutral point resistor rated current. The setting
OpModeSel
can be set to:
•
3I0Cosfi
where the current component is related to the set characteristic angle
relative to the reference voltage.
•
3I03V0Cosfi
where the power component is related to the set characteristic
angle relative to the reference voltage
•
3I0 and fi
, measuring the total residual current if the angle
fi
is within the set
range.
In this case
3I0Cosfi
is chosen.
2.
Set
DirMode
to
Forward
The setting
DirMode
can be set
Forward
or
Reverse
.
Forward
is chosen.
3.
Set
RCADir
to
0°
The setting
RCADir
(Relay Characteristic Angle) determines the angle between the
residual current and voltage giving maximum sensitivity. If a neutral point resistor
is used the setting
0°
is used. If capacitive residual current is measured (isolated
networks) the setting
-90°
is used.
4.
Set
RCAComp
to
0°
The setting
RCAComp
(Relay Characteristic Angle Compensation) can be used for
compensation of instrument transformer angle error.
5.
Set
ROADir
to
90°
The setting
ROADir
(Relay Open Angle) is the angle sector where the protection can
operate. Normally 90° is used. In special cases with very large capacitive current fed
from the line this sector can be limited to avoid unwanted trip at fault on another line.
6.
Set
INCosPhiPU
to
1.3 %
(corresponds to 13 A primary current)
The setting
INCosPhiPU
provides the sensitivity of the protection. Above, the
required current sensitivity (active ground fault current) is calculated to 13 A.
1MRK 506 334-UUS A
Section 3
REL650 setting examples
87
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...