7.2
Instantaneous phase overcurrent protection phase
segregated output SPTPIOC (50)
7.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Instantaneous phase overcurrent
protection, phase segregated output
SPTPIOC
3I>>
SYMBOL-Z V1 EN
50
7.2.2
Application
Long transmission lines often transfer great quantities of electric power from production
to consumption areas. The unbalance of the produced and consumed electric power at
each end of the transmission line is very large. This means that a fault on the line can easily
endanger the stability of a complete system. The transient stability of a power system
depends mostly on three parameters (at constant amount of transmitted electric power):
•
The type of the fault. Three-phase faults are the most dangerous, because no power
can be transmitted through the fault point during fault conditions.
•
The magnitude of the fault current. A high fault current indicates that the decrease of
transmitted power is high.
•
The total fault clearing time. The phase angles between the Electro motive forces
(EMFs) of the generators on both sides of the transmission line increase over the
permitted stability limits if the total fault clearing time, which consists of the
protection operating time and the breaker opening time, is too long.
The fault current on long transmission lines depends mostly on the fault position and
decreases with the distance from the generation point. For this reason the protection must
operate very quickly for faults very close to the generation (and relay) point, for which
very high fault currents are characteristic.
The instantaneous phase overcurrent protection phase segregated output SPTPIOC (50)
can operate in 10 ms for faults characterized by very high currents.
7.2.3
Setting guidelines
The parameters for Instantaneous phase overcurrent protection phase segregated output
SPTPIOC (50) are set via the local HMI or Protection and Control Manager (PCM600).
Section 7
1MRK 506 334-UUS A
Current protection
174
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...