7.7
Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
7.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sensitive directional residual over
current and power protection
SDEPSDE
-
67N
7.7.2
Application
In networks with high impedance grounding, the phase-to-ground fault current is
significantly smaller than the short circuit currents. Another difficulty for ground-fault
protection is that the magnitude of the phase-to-ground fault current is almost independent
of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-
ground faults in high impedance grounded networks. The protection uses the residual
current component 3I
0
· cos φ, where φ is the angle between the residual current and the
residual voltage (-3V
0
), compensated with a characteristic angle. Alternatively, the
function can be set to strict 3I
0
level with a check of angle 3I
0
and cos φ.
Directional residual power can also be used to detect and give selective trip of phase-to-
ground faults in high impedance grounded networks. The protection uses the residual
power component 3I
0
· 3V
0
· cos φ, where φ is the angle between the residual current and
the reference residual voltage, compensated with a characteristic angle.
A normal non-directional residual current function can also be used with definite or
inverse time delay.
A back-up neutral point voltage function is also available for non-directional sensitive
back-up protection.
In an isolated network, that is, the network is only coupled to ground via the capacitances
between the phase conductors and ground, the residual current always has -90º phase shift
compared to the reference residual voltage. The characteristic angle is chosen to -90º in
such a network.
In resistance grounded networks or in Petersen coil grounded, with a parallel resistor, the
active residual current component (in phase with the residual voltage) should be used for
the ground-fault detection. In such networks the characteristic angle is chosen to 0º.
Section 7
1MRK 506 334-UUS A
Current protection
214
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...