
The interlocking functionality in 650 series can not handle the transfer bus
(WA7)C.
To derive the signals:
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from any bay that contains the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and
each bus-coupler bay (ABC_BC) are needed:
Signal
189OPTR
189 is open.
289OPTR
289 is open (AB_TRAFO, ABC_LINE).
22089OTR
289 and 2089 are open (ABC_BC).
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
V22089TR
The switch status of 289 and 2089 are valid.
EXDU_BB
No transmission error from the bay that contains the above information.
If there is an additional bus-section disconnector, the signal from the bus-section
disconnector bay (A1A2_DC) must be used:
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If there is an additional bus-section circuit breaker rather than an additional bus-section
disconnector the signals from the bus-section, circuit-breaker bay (A1A2_BS) rather than
the bus-section disconnector bay (A1A2_DC) must be used:
1MRK 506 334-UUS A
Section 11
Control
361
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...