14.2.2
Application
SP16GGIO function block is used to send up to 16 logical signals to other systems or
equipment in the substation. Inputs should be connected in ACT tool.
14.2.3
Setting guidelines
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
14.3
IEC61850 generic communication I/O functions
MVGGIO
14.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC61850 generic communication I/O
functions
MVGGIO
-
-
14.3.2
Application
IEC61850 generic communication I/O functions (MVGGIO) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation.
It can also be used inside the same IED, to attach a RANGE aspect to an analog value and
to permit measurement supervision on that value.
14.3.3
Setting guidelines
The settings available for IEC61850 generic communication I/O functions (MVGGIO)
function allows the user to choose a deadband and a zero deadband for the monitored
signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and
low-low ranges of the measured value. The actual range of the measured value is shown
on the range output of MVGGIO function block. When a Measured value expander block
(MVEXP) is connected to the range output, the logical outputs of the MVEXP are changed
accordingly.
Section 14
1MRK 506 334-UUS A
Monitoring
428
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...