TMAGGIO 3 output signals and the physical outputs allows the user to adapt the signals
to the physical tripping outputs according to the specific application needs for settable
pulse or steady output.
13.3.3
Setting guidelines
Operation
: Turns the operation of the function
Enabled
/
Disabled
.
PulseTime
: Defines the pulse time duration. When used for direct tripping of circuit
breaker(s) the pulse time duration shall be set to approximately 0.150 seconds in order to
obtain satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
Used only for
ModeOutputx
:
Pulsed
.
OnDelay
: Used to prevent output signals to be given for spurious inputs. Normally set to
0 or a low value. Used only for
ModeOutputx
:
Steady
.
OffDelay
: Defines a minimum on time for the outputs. When used for direct tripping of
circuit breaker(s) the off delay time shall be set to approximately 0.150 seconds in order
to obtain a satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
Used only for
ModeOutputx
:
Steady
.
ModeOutputx
: Defines if output signal
OUTPUTx
(where x=1-3) is
Steady
or
Pulsed
. A
steady signal follows the status of the input signals, with respect to
OnDelay
and
OffDelay
. A pulsed signal will give a pulse once, when the
Outputx
rises from 0 to 1.
13.4
Configurable logic blocks
13.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
OR Function block
OR
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Inverter function block
INVERTER
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
PULSETIMER function block
PULSETIMER
-
-
1MRK 506 334-UUS A
Section 13
Logic
419
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...