11.5.10.3
Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar
connection could exist via the bus-section disconnector and bus-coupler within the other
bus section.
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
ABC_BC
ABC_LINE
ABC_BC
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
en04000479_ansi.vsd
ANSI04000479 V1 EN
Figure 186:
Busbars divided by bus-section disconnectors (circuit breakers)
The interlocking functionality in 650 series can not handle the transfer bus
(WA7)C.
To derive the signals:
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
BC_17_OP
No bus-coupler connection between busbar WA1 and WA7.
BC_17_CL
A bus-coupler connection exists between busbar WA1and WA7.
BC_27_OP
No bus-coupler connection between busbar WA2 and WA7.
BC_27_CL
A bus-coupler connection exists between busbar WA2 and WA7.
VP_BC_12
The switch status of BC_12 is valid.
VP_BC_17
The switch status of BC_17 is valid.
VP_BC_27
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC) are needed:
1MRK 506 334-UUS A
Section 11
Control
379
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...