The residual power, measured by the sensitive ground-fault protections in A and B will be:
0A
0A
0
S
3V
3I
=
×
EQUATION2026-ANSI V1 EN
(Equation 134)
0B
0B
0
S
3V
3I
=
×
EQUATION2027-ANSI V1 EN
(Equation 135)
The residual power is a complex quantity. The protection will have a maximum sensitivity
in the characteristic angle RCA. The apparent residual power component in the
characteristic angle, measured by the protection, can be written:
0A,prot
0A
0
A
S
3V
3I cos
=
×
×
j
EQUATION2028-ANSI V1 EN
(Equation 136)
0B,prot
0 B
0
B
S
3V
3I cos
=
×
×
j
EQUATION2029-ANSI V1 EN
(Equation 137)
The angles φ
A
and φ
B
are the phase angles between the residual current and the residual
voltage in the station compensated with the characteristic angle RCA.
The protection will use the power components in the characteristic angle direction for
measurement, and as base for the inverse time delay.
The inverse time delay is defined as:
0
0
inv
0
0
TDSN (3I 3V cos (reference))
t
3I 3V cos (measured)
f
f
×
×
×
=
×
EQUATION2069 V1 EN
(Equation 138)
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
1MRK 506 334-UUS A
Section 7
Current protection
219
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...