TDn
: Time multiplier for inverse time delay for step
n
.
IMinn
: Minimum operate current for step
n
in % of
IBase
. Set
IMinn
below
Pickupx
for
every step to achieve ANSI reset characteristic according to standard. If
IMinn
is set above
Pickupx
for any step then signal will reset at current equals to zero.
tnMin
: Minimum operating time for inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step
n
can never be shorter than the setting.
IEC09000164-2
Operate time
Current
tx
tnMin
IMinn
IEC09000164 V2 EN
Figure 99:
Minimum operate current and operate time for inverse time
characteristics
In order to fully comply with curves definition the setting parameter
txMin
shall be set to
the value which is equal to the operate time of the selected IEC inverse curve for measured
current of twenty times the set current pickup value. Note that the operate time value is
dependent on the selected setting value for time multiplier
TDn
.
7.6.3.2
Common settings for all steps
tx
: Definite time delay for step
x
. Used if definite time characteristic is chosen.
AngleRCA
: Relay characteristic angle given in degree. This angle is defined as shown in
figure
. The angle is defined positive when the residual current lags the reference
voltage (Vpol = 3V
0
or V
2
)
Section 7
1MRK 506 334-UUS A
Current protection
206
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...