Figure 100:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting range
is -180° to +180°.
polMethod
: Defines if the directional polarization is from
•
Voltage
(3V
0
or V
2
)
•
Current
(3I
0
· ZNpol or 3I
2
·ZNpol where ZNpol is RNpol + jXNpol), or
•
both currents and voltage,
Dual
(dual polarizing, (3V
0
+ 3I
0
· ZNpol) or (V
2
+ I
2
·
ZNpol)).
Normally voltage polarizing from the internally calculated residual sum or an external
open delta is used.
Current polarizing is useful when the local source is strong and a high sensitivity is
required. In such cases the polarizing voltage (3V
0
) can be below 1% and it is then
necessary to use current polarizing or dual polarizing. Multiply the required set current
(primary) with the minimum impedance (ZNpol) and check that the percentage of the
phase-to-ground voltage is definitely higher than 1% (minimum 3V
0
>
VPolMin
setting) as
a verification.
RNPol, XNPol
: The zero-sequence source is set in primary ohms as base for the current
polarizing. The polarizing voltage is then achieved as 3I
0
· ZNpol. The ZNpol can be
defined as (ZS
1
-ZS
0
)/3, that is the ground return impedance of the source behind the
1MRK 506 334-UUS A
Section 7
Current protection
207
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...