Figure 72:
The voltage increase on healthy phases and occurring neutral point
voltage (3V0) at a single phase-to-ground fault and an occurring cross-
country fault on different feeders in a sub-transmission network, high
impedance (resistance, reactance) grounded
PPLPHIZ is connected between Five zone distance protection, quadrilateral characteristic
function (ZQMPDIS, 21) and Phase selection with load encroachment, quadrilateral
characteristic function FDPSPDIS (21) as shown in figure
. The integer from the phase
selection function, which gives the type of fault undergoes a check and will release the
distance protection zones as decided by the logic. The logic includes a check of the fault
loops given by the phase selection and if the fault type indicates a two or three phase fault
the integer releasing the zone is not changed.
If the fault indicates and ground-fault checks are done which mode of tripping to be used,
for example ABCAc, which means that fault in the phases are tripped in the cyclic order A
before B before C before A. Local conditions to check the phase-to-ground voltage levels
and occurring zero sequence current and voltages completes the logic.
Section 6
1MRK 506 334-UUS A
Impedance protection
154
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...