![ABB REL650 series Applications Manual Download Page 134](http://html1.mh-extra.com/html/abb/rel650-series/rel650-series_applications-manual_3479164134.webp)
R
X
Zm
RldRev
R
Zm
RLdFwd
ZL
ANSI05000495_2_en.vsd
Load impedance area in
forward direction
LdAngle
LdAngle
LdAngle
LdAngle
ANSI05000495 V2 EN
Figure 61:
Load encroachment phenomena and shaped load encroachment
characteristic defined in Phase selection with load encroachment
function FDPSPDIS (21)
jX
R
Load
Load
Load
Load
jX
R
Load
Load
Load
Load
No
operation
en06000403.vsd
IEC06000403 V1 EN
Figure 62:
Load encroachment phenomena and shaped load encroachment
characteristic
The load encroachment algorithm will increase the possibility to detect high fault
resistances, especially for phase to ground faults at remote line end. For example, in
quadrilateral characteristic, a given setting of the load angle
LdAngle
for phase selection
with load encroachment, the resistive blinder for the zone measurement can be expanded
according to the figure
given higher fault resistance coverage without risk for
unwanted operation due to load encroachment. This is valid in both directions. Again, for
example in mho characteristic, for a given setting of the load angle
LdAngle
(see
figure
), the zone reach can be expanded according to the diagram on the right in
given higher fault resistance coverage without risk for unwanted operation due
Section 6
1MRK 506 334-UUS A
Impedance protection
128
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...