specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, except in the
following cases:
•
989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B
•
152_EX3 in module AB_TRAFO
when they are set to 0=FALSE.
11.5.4
Interlocking for busbar grounding switch BB_ES (3)
11.5.4.1
Application
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one busbar
grounding switch on any busbar parts according to figure
89G
en04000504.vsd
ANSI04000504 V1 EN
Figure 151:
Switchyard layout BB_ES (3)
The signals from other bays connected to the module BB_ES are described below.
11.5.4.2
Signals in single breaker arrangement
The busbar grounding switch is only allowed to operate if all disconnectors of the bus-
section are open.
en04000505_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
ABC_LINE
BB_ES
ABC_LINE
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
BB_ES
ABC_BC
ANSI04000505 V1 EN
Figure 152:
Busbars divided by bus-section disconnectors (circuit breakers)
Section 11
1MRK 506 334-UUS A
Control
348
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...