178 Parameters
The electrical statuses of the relay/digital outputs can be
overridden for eg. testing purposes. A bit in parameter
is provided for each relay or digital output,
and its value is applied whenever the corresponding bit in this
parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
and
).
0000h
0000h…FFFFh
Override selection for relay/digital outputs.
1 = 1
Allows the data value of a forced relay or digital output to be
changed from 0 to 1. It is only possible to force an output that
has been selected in parameter
Bits 0…1 are the forced values for RO4…RO5; bit 5 is the
forced value for DO1.
0000h
0000h…FFFFh
Forced values of relay/digital outputs.
1 = 1
Selects a drive signal to be connected to relay output RO4.
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
(see page
).
2
Reserved
3
Enabled
(see page
). 4
Started
(see page
).
5
Magnetized
(see page
).
6
Running
(see page
).
7
Ready ref
(see page
).
8
At setpoint
(see page
).
9
Reverse
(see page
).
10
Zero speed
(see page
).
11
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force RO4 to value of bit 0 of parameter
1
1 = Force RO5 to value of bit 1 of parameter
2…4
Reserved
5
1 = Force DO1 to value of bit 5 of parameter
6…15
Reserved
Bit
Name
Description
0
RO4
Force the value of this bit to RO4, if so defined in parameter
.
1
RO5
Force the value of this bit to RO5, if so defined in parameter
.
2…4
Reserved
5
DO1
1Force the value of this bit to DO1 if so defined in parameter
.
6…15
Reserved