Drive status word 1.
This parameter is read-only.
-
0000hTFFFFh
Drive status word 1.
1 = 1
Drive status word 2.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 2.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Enabled
1 = Both run enable (see par.
) and start enable (
) signals
are present.
Note:
This bit is not affected by the presence of a fault.
1
Inhibited
1 = Start inhibited. To start the drive, the inhibiting signal (see par.
) must be removed and the start signal cycled.
2
DC charged
1 = DC circuit has been charged
3
Ready to start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control
1 = Drive is in local control
9
Network control
1 = Drive is in
(see page
).
10
Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12
Reserved
13
Start request
1 = Start requested. 0 = When Enable to rotate signal (see par.
) is 0 (rotating of the motor is disabled).
14…15 Reserved
Bit
Name
Description
0
Identification run done 1 = Motor identification (ID) run has been performed
1
Magnetized
1 = The motor has been magnetized
2
Torque control
1 = Torque control mode active
3
Speed control
1 = Speed control mode active
4
Reserved
5
Safe reference active 1 = A “safe” reference is applied by functions such as
6
Last speed active
1 = A “last speed” reference is applied by functions such as
parameters
7
Loss of reference
1 = Reference signal lost
8
Emergency stop failed 1 = Emergency stop failed (see parameters
and
9
Jogging active
1 = Jogging enable signal is on
10…12 Reserved
13
Start delay active
1 = Start delay (par.
) active.
14…15 Reserved
ACS580 FW.book Page 155 Wednesday, September 21, 2016 9:48 PM