Parameters 301
Data storage parameter 18.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 19.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 20.
0
-32768…32767
16-bit data.
1 = 1
49
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note:
For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
is taken.
10.0 s
0.3…3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
Selects how the drive reacts to a control panel (or PC tool)
communication break.
No action
No action taken.
0
Fault
1
Last speed
Drive generates an
warning and freezes the
speed to the level the drive was operating at. The speed is
determined on the basis of actual speed using 850 ms low-
pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe
Drive generates an
warning and sets the
speed to the speed defined by parameter
(or
when frequency reference
is being used).
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Applies the settings of parameters
.
Note:
Refreshing may cause a communication break, so
reconnecting the drive may be required.
Done
Refresh done or not requested.
0
No.
Name/Value
Description
Def/FbEq16