270 Parameters
Defines the motor load curve together with parameters
and
The load curve is
used by the motor thermal protection model to estimate the
motor temperature.
When the parameter is set to 100%, the maximum load is
taken as the value of parameter
(higher loads heat up the motor). The load curve level should
be adjusted if the ambient temperature differs from the
nominal value set in
100%
50…150%
Maximum load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
. Defines the
maximum motor load at zero speed of the load curve. A
higher value can be used if the motor has an external motor
fan to boost the cooling. See the motor manufacturer's
recommendations.
See parameter
100%
50…150%
Zero speed load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
. Defines the
break point frequency of the load curve ie. the point at which
the motor load curve begins to decrease from the value of
parameter
towards the value of
parameter
45.00 Hz
1.00…500.00 Hz
Break point for the motor load curve.
See par.
No.
Name/Value
Description
Def/FbEq16
50
100
150
I/I
N
(%)
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
ACS580 FW.book Page 270 Wednesday, September 21, 2016 9:48 PM