Parameters 283
Timed function 1
Bit 0 of
(see page
).
18
Timed function 2
Bit 1 of
(see page
).
19
Timed function 3
Bit 2 of
(see page
).
20
Supervision 1
Bit 0 of
(see page
).
21
Supervision 2
Bit 1 of
(see page
).
22
Supervision 3
Bit 2 of
(see page
).
23
Source selection (see
). -
Internal process setpoint 1. See parameter
.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 1.
1 = 1 PID
customer unit
Internal process setpoint 2. See parameter
.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 2.
1 = 1 PID
customer unit
Internal process setpoint 3. See parameter
.
0.00 PID
customer
units
-32768.00…
32767.00 PID
customer units
Internal process setpoint 3.
1 = 1 PID
customer unit
Defines a minimum limit for the process PID controller
setpoint.
0.00
-32768.00…
32767.00
Minimum limit for process PID controller setpoint.
1 = 1
Defines a maximum limit for the process PID controller
setpoint.
32767.00
-32768.00…
32767.00
Maximum limit for process PID controller setpoint.
1 = 1
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
0.0 s
0.0…1800.0 s
Setpoint increase time.
1 = 1
Defines the minimum time it takes for the setpoint to decrease
from 100% to 0%.
0.0 s
0.0…1800.0 s
Setpoint decrease time.
1 = 1
Freezes, or defines a source that can be used to freeze, the
setpoint of the process PID controller. This feature is useful
when the reference is based on a process feedback
connected to an analog input, and the sensor must be
serviced without stopping the process.
1 = Process PID controller setpoint frozen
See also parameter
.
Not selected
Process PID controller setpoint not frozen.
0
Selected
Process PID controller setpoint frozen.
1
DI1
Digital input DI1 (
, bit 0).
2
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 283 Wednesday, September 21, 2016 9:48 PM