Parameters 249
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter
) is compared
to its lower and upper limits (
and
respectively).
The action to be taken when the condition is fulfilled is
selected by
.
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever the signal falls below its lower limit.
1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note:
This parameter does not affect the status indicated by
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
Fault if running
If running, the drive trips on fault
3
Selects the signal to be monitored by signal supervision
function 1.
Zero
None.
0
Speed
(page
).
1
Reserved
2
Frequency
3
Current
4
Reserved
5
Torque
). 6
DC voltage
(page
).
7
Output power
(page
).
8
AI1
(page
).
9
AI2
).
10
Reserved
11…17
Speed ref ramp in
).
18
Speed ref ramp out
(page
19
Speed ref used
(page
).
20
Torque ref used
(page
).
21
Freq ref used
).
22
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 249 Wednesday, September 21, 2016 9:48 PM