388 Fault tracing
AFED Enable to rotate
Signal to rotate has not been
received within a fixed time
delay of 120 s.
Switch enable to rotate signal on (eg. in
digital inputs).
Check the setting of (and source
selected by) parameter
AFF6
Identification run
Motor ID run will occur at next
start.
Informative warning.
B5A0
STO event
Programmable event:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is lost.
Check safety circuit connections. For
more information, see chapter
The Safe
torque off function
in the
Hardware
manual
of the drive and description of
parameter
(page
).
Code
(hex)
Warning / Aux. code
Cause
What to do
ACS580 FW.book Page 388 Wednesday, September 21, 2016 9:48 PM