246 Parameters
Fault/Event
2
Warning/Warning
3
Selects how the drive reacts to incorrect input power and
motor cable connection (ie. input power cable is connected to
drive motor connection).
No action
No action taken.
0
Fault
.
1
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
, and
• the output frequency is below the level set by parameter
or the motor speed is below the
level set by parameter
, and
• the conditions above have been true longer than the time
set by parameter
.
No action
None (stall supervision disabled).
0
Warning
The drive generates an
warning.
1
Fault
2
Stall current limit in percent of the nominal current of the
motor. See parameter
.
200.0%
0.0…1600.0%
Stall current limit.
-
Stall speed limit in rpm. See parameter
150.00 rpm
0.00…10000.00
rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
.
Note:
Setting the limit below 10 Hz is not recommended.
15.00 Hz
0.00…1000.00 Hz
Stall frequency limit.
See par.
No.
Name/Value
Description
Def/FbEq16
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Fault
Event
0
1
Faults
Event
and fault
1
0
Faults
Event
and fault
1
1
(Normal operation)
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Warning
0
1
Warning
1
0
Warning
1
1
(Normal operation)