410 Fieldbus control through the embedded fieldbus interface (EFB)
2
REVERSE
1
Reverse direction of motor rotation. See in the table
below how this bit and sign of the reference effect the
direction of the motor direction.
0
(no op)
3
Reserved
4
RESET
0=>1
Fault reset if an active fault exists.
0
(no op)
5
EXT2
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
6
RUN_DISABLE
1
Run disable. If the drive is set to receive the run enable
signal from the fieldbus, this bit deactivates the signal.
0
Run enable. If the drive is set to receive the run enable
signal from the fieldbus, this bit activates the signal.
7
STOPMODE_RA
MP
1
Normal ramp stop mode
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
8
STOPMODE_EM
ERGENCY_RAM
P
1
Emergency ramp stop mode.
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
9
STOPMODE_CO
AST
1
Coast stop mode.
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
10
RAMP_PAIR _2
1
Select ramp set 2 (Acceleration time 2 / Deceleration time
is set to
.
0
Select ramp set 1 (Acceleration time 1 / Deceleration time
is set to
.
11
RAMP_OUT_ZER
O
1
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
0
Normal operation.
12
RAMP_HOLD
1
Halt ramping (Ramp Function Generator output held).
0
Normal operation.
13
RAMP_IN_ZERO
1
Force Ramp Function Generator input to zero.
0
Normal operation.
Bit
Name
Value
State/Description
Sign of the reference
Positive (+)
Negative (-)
Bit REVERSE = 0
Forward
Reverse
Bit REVERSE = 1
Reverse
Forward
ACS580 FW.book Page 410 Wednesday, September 21, 2016 9:48 PM