94 Program features
Settings
Parameter groups
(page
) and
(page
).
Programmable relay outputs
The control unit has three relay outputs. The signal to be indicated by the outputs can
be selected by parameters.
Two relay outputs can be added by using a CMOD-01 multifunction extension module
or a CHDI-01 115/230 V digital input extension module.
Settings
Parameter group
(page
).
Programmable I/O extensions
Inputs and outputs can be added by using a CMOD-01 multifunction extension
module or a CHDI-01 115/230 V digital input extension module. The module is
mounted on option slot 2 of the control unit.
The table below shows the number of I/O on the control unit as well as optional
CMOD-01 and a CHDI-01 modules.
The I/O extension module can be activated and configured using parameter group
15.
Note:
The configuration parameter group contains parameters that display the values
of the inputs on the extension module. These parameters are the only way of utilizing
the inputs on an I/O extension module as signal sources. To connect to an input,
choose the setting
Other
in the source selector parameter, then specify the
appropriate value parameter (and bit, for digital signals) in group 15.
Settings
Parameter group
(page
Fieldbus control
The drive can be connected to several different automation systems through its
fieldbus interfaces. See chapters
Fieldbus control through the embedded fieldbus
(page
) and
Fieldbus control through a fieldbus adapter
(page
Location
Digital
inputs
(DI)
Digital
outputs
(DO)
Digital
I/Os
(DIO)
Analog
inputs
(AI)
Analog
outputs
(AO)
Relay
outputs
(RO)
Control unit
6
-
-
2
2
3
CMOD-01
-
1
-
-
-
2
CHDI-01
6 (115/230 V)
-
-
-
-
2
ACS580 FW.book Page 94 Wednesday, September 21, 2016 9:48 PM