Parameters 275
The date on which amplitude logger 2 was last reset.
01.01.1980
-
Last reset date of amplitude logger 2.
-
The time at which amplitude logger 2 was last reset.
00:00:01
-
Last reset time of amplitude logger 2.
-
37
Settings for user load curve.
See also section
).
Displays the status of the monitored signal.
0000h
0000h…FFFFh
Status of the monitored signal.
1 = 1
Selects the signal to be supervised.
Not selected
No signal selected. ULC disabled.
0
Motor speed %
(page
1
Motor current %
(page
).
2
Motor torque %
3
Output power % of
motor nominal
(page
).
4
Output power % of
drive nominal
(page
). 5
Source selection (see
). -
Selects an action taken if the signal stays over the overload
curve for a defined time.
Disabled
No warnings or fault generated.
0
Warning
The drive generates an
if the
signal has been continuously over the overload curve for a
time defined by parameter
.
1
Fault
The drive generates an
if the signal
has been continuously over the overload curve for a time
defined by parameter
.
2
Warning/Fault
The drive generates an
if the
signal has been continuously over the overload curve for half
of the time defined by parameter
.
The drive generates an
if the signal
has been continuously over the overload curve for a time
defined by parameter
.
3
Selects an action taken if the signal stays under the
underload curve for a defined time.
Disabled
No warnings or fault generated.
0
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Under load limit
1 = Signal lower than the underload curve.
1
Within load range
1 = Signal between the underload and overload curve.
2
Overload limit
1 = Signal higher than the overload curve.
3…15
Reserved
ACS580 FW.book Page 275 Wednesday, September 21, 2016 9:48 PM