Parameters 245
Fault
The drive trips on fault
2
Selects how the drive reacts when a supply phase loss is
detected.
No action
No action taken.
0
Fault
The drive trips on fault
.
1
Selects which indications are given when one or both Safe
torque off (STO) signals are switched off or lost. The
indications also depend on whether the drive is running or
stopped when this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the STO
function itself. The STO function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
• The loss of only one STO signal always generates a fault
as it is interpreted as a malfunction.
For more information on the STO, see chapter
The Safe
torque off function
in the
Hardware manual
of the drive.
Fault/Fault
0
Fault/Warning
1
No.
Name/Value
Description
Def/FbEq16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
0
1
and
1
0
and
1
1
(Normal operation)
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Fault
Warning
0
1
Faults
and
Warning
and fault
1
0
Faults
and
Warning
and fault
1
1
(Normal operation)