Parameters 313
Selects the type and scaling of reference 2 received through
the embedded fieldbus interface.
The scaled reference is displayed by
Selects the type of actual value 1.
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows.
0
Transparent
No scaling is applied.
1
General
Generic reference without a specific unit. Scaling: 1 = 100.
2
Torque
Scaling is defined by parameter
3
Speed
Scaling is defined by parameter
4
Frequency
Scaling is defined by parameter
.
5
Selects the type of actual value 2.
For the selections, see parameter
.
Selects the source of actual value 1 when parameter
is set to
Not selected
None.
0
Source selection (see
). -
Selects the source of actual value 2 when parameter
is set to
(par.
)
Not selected
None.
0
Source selection (see
). -
Defines the mapping between parameters and holding
registers in the 400101…465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
(
Mode 0
16-bit values (groups 1…99, indexes 1…99):
Register address = 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 2200 + 80 = 402280.
32-bit values (groups 1…99, indexes 1…99):
Register address = 200 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 4400 + 160 = 424560.
0
Mode 1
16-bit values (groups 1…255, indexes 1…255):
Register address = 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 5632 + 80 = 405712.
1
Mode 2
32-bit values (groups 1…127, indexes 1…255):
Register address = 512 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 11264 + 160 = 411424.
2
No.
Name/Value
Description
Def/FbEq16
Operation mode
Actual 1 type
Speed control
Torque control
Frequency control
ACS580 FW.book Page 313 Wednesday, September 21, 2016 9:48 PM