Parameters 325
Enable
Adaptive voltage limits enabled.
1
AC supply voltage estimated by calculation. Estimation is
done every time the drive is powered up and is based on the
rise speed of voltage level of the DC bus while the drive
charges the DC bus.
-
0…65535 V
Voltage.
10 = 1 V
Specifies how the control board of the drive is powered.
Internal 24V
The drive control board is powered from the drive power unit
it is connected to.
0
External 24V
The drive control board is powered from an external power
supply.
1
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note:
The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
-
0000b…0111b
Hardware options configuration word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
EX motor
1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors
Notes:
• For non-ABB Ex motors, use parameters
to
define the correct minimum switching frequency.
• If you have a multimotor system, contact your local ABB
representative.
1
ABB Sine filter
1 = An ABB sine filter is connected to the output of the drive.
2…15
Reserved
ACS580 FW.book Page 325 Wednesday, September 21, 2016 9:48 PM