Fault tracing 391
4110
Control board
temperature
Control board temperature is
too high.
Check proper cooling of the drive.
Check the auxiliary cooling fan.
4210
IGBT overtemperature Estimated drive IGBT
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4290
Cooling
Drive module temperature is
excessive.
Check ambient temperature. If it exceeds
40 °C/104 °F (IP21 frames R4
…
R9) or if
it exceeds 50 °C /122 °F (IP21 frames
R0
…
R9), ensure that load current does
not exceed derated load capacity of
drive. For all P55 frames, check the
derating temperatures. See chapter
Technical data
, section
Derating
in the
Hardware manual
of the drive.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
42F1
IGBT temperature
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4310
Excess temperature
Power unit module
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4380
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases.
Check the motor cabling.
Check cooling of drive module(s).
4981
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded fault limit.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
4982
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded fault limit.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
4991
Safe motor
temperature
The CPTC-02 module
indicates overtemperature.
• motor temperature is too
high, or
• the thermistor is in short-
circuit or disconnected.
Check the cooling of the motor.
Check the motor load and drive ratings.
Check the wiring of the temperature
sensor.Repair wiring if faulty.
Measure the resistance of the sensor.
Replace the sensor if faulty.
4993
CPTC-02
Safe motor temperature is
enabled but the CPTC-02
module is not detected
(parameter
Power down the control unit and check
that the module is properly inserted in the
correct slot.
Code
(hex)
Fault / Aux. code
Cause
What to do
ACS580 FW.book Page 391 Wednesday, September 21, 2016 9:48 PM