316 Parameters
Displays status information on process external PID control.
This parameter is read-only.
-
0000h…FFFFh
Process PID control status word.
1 = 1
.
0.000 s
Defines, together with parameter
, a
general scaling factor for the external PID control chain. The
scaling can be utilized when, for example, the process
setpoint is input in Hz, and the output of the PID controller is
used as an rpm value in speed control. In this case, this
parameter might be set to 50, and parameter
to the
nominal motor speed at 50 Hz.
In effect, the output of the PID controller [
] when
deviation (setpoint - feedback) = [
] = 1.
Note:
The scaling is based on the ratio between
. For example, the values 50 and 1500 would produce
the same scaling as 1 and 3.
1500.00
-32768.00…
32767.00
Process setpoint base.
1 = 1
1500.00
-32768.00…
32767.00
Process PID controller output base.
1 = 1
.
.
0.00 PID
customer
units
0.00 PID
customer
units
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
PID active
1 = Process PID control active.
1
Reserved
2
Output frozen
1 = Process PID controller output frozen. Bit is set if parameter
is TRUE, or the deadband function is
active (bit 9 is set).
3…6
Reserved
7
Output limit high
1 = PID output is being limited by par.
8
Output limit low
1 = PID output is being limited by par.
9
Deadband active
1 = Deadband is active.
10…11 Reserved
12
Internal setpoint
active
1 = Internal setpoint active (see par.
…
13…15 Reserved
ACS580 FW.book Page 316 Wednesday, September 21, 2016 9:48 PM