168 Parameters
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
4.000 mA or
0.000 V
0.000…20.000 mA
or 0.000…10.000 V
Minimum value of AI1.
1000 = 1 unit
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
20.000 mA or
10.000 V
0.000…20.000 mA
or 0.000…10.000 V
Maximum value of AI1.
1000 = 1 unit
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
. (Changing the polarity settings of
and
can effectively invert the analog input.)
0.000
-32768.000…
32767.000
Real value corresponding to minimum AI1 value.
1 = 1
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
. See the drawing at parameter
.
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI1 value.
1 = 1
Displays the value of analog input AI2 in mA or V (depending
on whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
-
0.000…20.000 mA
or 0.000…10.000 V
Value of analog input AI2.
1000 = 1 unit
Displays the value of analog input AI2 after scaling. See
parameters
and
.
This parameter is read-only.
-
-32768.000…
32767.000
Scaled value of analog input AI2.
1 = 1
No.
Name/Value
Description
Def/FbEq16
AI
in
AI
scaled
)
ACS580 FW.book Page 168 Wednesday, September 21, 2016 9:48 PM