170 Parameters
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
See the drawing at parameter of
.
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
Value of analog input AI1 in percent of AI1 scaling (
-
).
-
0.00…100.00%
AI1 value
100 = 1%
Value of analog input AI2 in percent of AI2 scaling (
-
).
-
0.00…100.00%
AI2 value
100 = 1%
13
Configuration of standard analog outputs.
The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
and
0000h
0000h…FFFFh
Forced values selector for analog outputs AO1 and AO2.
1 = 1
Displays the value of AO1 in mA or V.
This parameter is read-only.
-
0.000…22.000 mA /
0.000…11.000 V
Value of AO1.
1 = 1 mA
Selects a signal to be connected to analog output AO1.
Zero
None. 0
Motor speed used
(page
1
Reserved
2
Output frequency
(page
3
Motor current
4
Motor current % of
motor nominal
5
Motor torque
(page
).
6
DC voltage
(page
).
7
Output power
). 8
Reserved
9
Speed ref ramp in
(page
10
Speed ref ramp out
(page
).
11
Speed ref used
12
Reserved
13
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force AO1 to value of parameter
. (0 = Normal mode)
1
1 = Force AO2 to value of parameter
. (0 = Normal mode)
2…15
Reserved
ACS580 FW.book Page 170 Wednesday, September 21, 2016 9:48 PM