Parameters 281
Control panel (ref
saved)
Panel reference (
)
saved by the control system for the location where the control
returns is used as the reference.
13
Control panel (ref
copied)
Panel reference (
) for
the previous control location is used as the reference when
the control location changes if the references for the two
locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal is
used as the new reference.
14
FB A ref1
(see page
15
FB A ref2
(see page
16
Reserved
17…18
EFB ref1
19
EFB ref2
20
Reserved
21…23
Setpoint data
storage
24
Source selection (see
). -
Selects the second source of process setpoint. The second
source is used only if the setpoint function requires two
inputs.
For the selections, see parameter
Selects a function between the setpoint sources selected by
parameters
and
In1 Source
1.
0
In1+In2
Sum of sources 1 and 2.
1
In1-In2
Source 2 subtracted from source 1.
2
In1*In2
Source 1 multiplied by source 2.
3
In1/In2
Source 1 divided by source 2.
4
MIN(In1,In2)
Smaller of the two sources.
5
MAX(In1,In2)
Greater of the two sources.
6
AVE(In1,In2)
Average of the two sources.
7
sqrt(In1)
Square root of source 1.
8
No.
Name/Value
Description
Def/FbEq16
Ext1 -> Ext2
t
Reference
Ext1 reference
Ext2 reference
Active reference
Inactive reference
Ext1 -> Ext2
Ext1 reference
Ext2 reference
Active reference
t
Inactive reference
Reference