Parameters 149
Current day energy consumption. This is the energy of the
last 24 hours (not necessarily continuous) the drive has been
running, not the energy of a calendar day. The value is set to
the value before the power cycle when the drive is again up
and running.
-
0.00… 1000000.00
kWh
Energy.
1 = 1 kWh
Previous day energy consumption. The value
is stored here when its value has been cumulated
for 24 hours. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy.
1 = 1 kWh
Absolute value of parameter
.
-
0.00… 30000.00
rpm
Estimated motor speed.
See par.
Absolute value of parameter
-
0.00… 1000.00%
Estimated motor speed.
10 = 1%
Absolute value of parameter
-
0.00…500.00 Hz
Estimated output frequency.
See par.
Absolute value of parameter
-
0.0…1600.0%
Motor torque.
See par.
Absolute value of parameter
.
-
0.00… 32767.00
kW or hp
Output power.
1 = 1 kW
Absolute value of parameter
.
-
0.00… 300.00%
Output power.
1 = 1%
Absolute value of parameter
.
-
0.00… 300.00%
Output power.
1 = 1%
Absolute value of parameter
-
0.00… 32767.00
kW or hp
Motor shaft power.
1 = 1 kW
03
Values of references received from various sources.
All parameters in this group are read-only unless otherwise
noted.
Reference 1 given from the control panel or PC tool.
-
-100000.00…
100000.00
Control panel or PC tool reference.
1 = 10
No.
Name/Value
Description
Def/FbEq16
ACS580 FW.book Page 149 Wednesday, September 21, 2016 9:48 PM