116 Program features
continues.
Settings
Parameters
Post-magnetization
The function keeps the motor magnetized for a certain period (parameter
) after stopping. This is to prevent the machinery from moving
under load, for example before a mechanical brake can be applied. Post-
magnetization is activated by parameter
. The magnetization
Note:
Post-magnetization is only available when ramp stop is selected (see
). Post-magnetization is only supported in vector control.
Settings
Parameters
(page
),
and
Pre-heating (Motor heating)
The pre-heating function keeps the motor warm and prevents condensation inside the
motor by feeding it with DC current when the drive has been stopped. The heating
can only be on when the drive is in the stopped state, and starting the drive stops the
heating.
When pre-heating is activated and the stop command is given, pre-heating starts
immediately if the drive is running below zero speed (see bit 0 in parameter
). If the drive is running above zero speed, pre-heating is
delayed by 60 seconds to prevent excessive current.
Reference
Motor speed
DC hold
t
t