ZP3 Fire Control Panel
Field Wiring
ZP3 Fire Control Panel Manual
Page 5 - 8
UD1160.5 Iss 6 (25/02/2005)
I
5
5.4.2 Common Fire / Fault Outputs
The common fire and common fault relay outputs provide voltage free contacts which can be
set to be either normally-open (closing on alarm), or normally-closed (opening on alarm).
The N/O or N/C settings are done in software, in the setup menu.
The common fire relay changes state on any fire alarm, and the common fault relay changes
state on any fault alarm. Relays restore when the panel is reset.
The relay contacts are rated for a maximum current of 1 ampere, and a maximum voltage of
24VDC, or 100 VAC.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......