ZP3 Fire Control Panel
System Configuration
ZP3 Fire Control Panel Manual
UD1160.7 Iss 6 (25/02/2005)
Page 7 - 7
I
7
Sounders/Control Outputs
Each output that is defined to operate sounders, should be specified as such. Note that
outputs declared as a sounders will always be silencing, and this setting takes precedence
over the I/O mapping setting. Outputs defined to operate as control outputs should be
defined as such.
7.3.2 Input-Output Mapping
Input parameters
Input Mode
The input can be set to operate its linked output as either Steady, Flash Fast, Flash Slow, or
Disable. The "Disable" option is used when an input address, such as a keyswitch, is used
to disable one or more outputs, for example for routine maintenance. Note that panel
outputs can be set to fast or slow intermittent operation, whereas Z-loop devices have only
one flash rate.
Input Device Type
The device type of the input may be defined as a general device, line device, or a gas control
unit. The type setting determines what trigger events are available to activate an output.
Trigger
Each input can be set to trigger the output on certain types of event, defined by its type.
Sensors can activate outputs from fire, fault, pre-alarm, service or disabled alarms.
7.3.3 Point Address Structure
Input /Output mapping is a software defined rule that defines a set of input triggers that will
activate an output. One or more inputs may be linked to a output. Each input and output has
an address which must be specified when setting an I/O mapping link. Each address consist
of three elements as follows.
00- 00- 000
Panel number, two digits
Group or loop number, two digits
Point address, three digits
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......