ZP3 Fire Control Panel
Software Programming
ZP3 Fire Control Panel Manual
Page 6 - 16
UD1160.6 Iss 6 (25/02/2005)
I
6
System configuration: Relays
Menu Path:
Setup\System
Configuration|Relays
The System Configuration menu is used to set the common functions of the panel. The
"Relays" menu allows for the setup of the standard built-in relays.
Fire Relay
The common fire relay can be set to normally de-
energised (open contact, closing on alarm) or normally
energised (closed contact, open on alarm). The latter
state is described as "inverted" in the menu.
Fault Relay
The common fault relay can be set to normally energised
(open contact, closing on alarm) or normally de-
energised (closed contact, open on alarm). The latter
state is described as "inverted" in the menu.
RMC Alarm
The remote manned centre output is connected to RMC-
routing equipment. It should be set to restore only after a
reset.
Sounder Relays
The sounder outputs (4 outputs, controlled from 2
addresses) can be set to operate as "common", from any
alarm, or as programmable. If set to programmable, then
they must be linked to activating inputs in the I/O-menu.
System configuration: Printer
Menu Path:
Setup\System
Configuration|Printer
The System Configuration menu is used to set the common functions of the panel. The
"Printer" menu allows for the setup of the optional in-panel printer.
Printer type
Allows the type of printer to be defined. Current types
are:
NONE
(no printer attached)
Able24
(panel
printer)
or IN
(panel printer)
Serial desktop
(external printer 80 column)
Printer options
Defines the information to be printed. Categories are
"Fire Alarms", "Fault Alarms", "Panel Operations", and
"Outputs Active."
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......