ZP3 Fire Control Panel
Maintenance
ZP3 Fire Control Panel Manual
Page 1 - 22
UD1160.M Iss 6 (25/02/2005)
I
M
Device Type
Sensitivity level
High
Standard
Medium
Low
Nom
Max
Nom
Max
Nom
Max
Nom
Max
ZP710-2
N+68 168 N+81 180 N+94 190 N+105 200
ZP720-2
145
N/A
a(144) N/A
a(187) N/A
188
N/A
ZP720-3
25 179 25 163 25 179 25 163
ZP725-2
125 N/A 153 N/A 176 N/A 196 N/A
ZP730-2
N+77 158 N+90 176 N+102 186 N+110 205
ZP732-2
N+77 158 N+90 176 N+102 186 N+110 205
ZP720-3
165
N/A
a(164) N/A
a(180) N/A
181
N/A
ZP5-IF8
138 187 138 187 138 187 138 187
ZP740-2
138 187 138 187 138 187 138 187
ZP745
138 187 138 187 138 187 138 187
ZP770-2
138 187 138 187 138 187 138 187
ZP740ST
150 255 150 255 150 255 150 255
ZP755
N/A N/A N/A N/A N/A N/A N/A N/A
ZP750-2
141 141 141 141 141 141 141 141
ZP752-2
N/A N/A N/A N/A N/A N/A N/A N/A
ZP753-2
N/A N/A N/A N/A N/A N/A N/A N/A
ZP754*-2
N/A N/A N/A N/A N/A N/A N/A N/A
ZX832-2
N+49 255 N+60 255 N+80 255 N+105 255
ZR420
181 181 181 181 181 181 181 181
ZR430
181 181 181 181 181 181 181 181
Radio
Sounder
181 181 181 181 181 181 181 181
ZP710Ex-1
N+34 255 N+40 255 N+47 255 N+52 255
ZP720Ex-1
73 N/A 73 N/A 95 N/A 102 N/A
ZP785-2
138 187 138 187 138 187 138 187
ZP785-3
138 187 138 187 138 187 138 187
ZP786Ex-1
59 98 59 98 59 98 59 98
ZP740Ex-1
59 98 59 98 59 98 59 98
ZP5-570-2
138 187 138 187 138 187 138 187
ZP5-574
138 187 138 187 138 187 138 187
Note*:
When the calculated "N+" values fall outside of the Minimum/Maximum levels, the
Minimum/Maximum levels take precedence. N is the nominal idle value read on a daily
basis. N value adjustment is limited to 10 counts Max. This avoids sensitivity shift in a
smoldering fire situation.
‘a’
=
algorithm
Table 1.4.3 Analogue status – alarm values
In Table 1.4.3 the analogue values that indicate an alarm state are shown for various
devices. For some devices other value ranges are used to indicate such conditions as fault,
service, pre-service and pre-alarm.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......