ZP3 Fire Control Panel
Software Programming
ZP3 Fire Control Panel Manual
UD1160.6 Iss 6 (25/02/2005)
Page 6 - 17
I
6
System configuration: [Various]
Menu Path:
Setup\System Configuration|[as below]
The System Configuration menu is used to set the common functions of the panel. This
section describes various other options available in this menu.
Silence delay
Allows the SILENCE ALARMS key to be delayed to
prevent the alarm sounders from being silenced (turned
off) too soon, before being heard. Enter the required
silence delay time required in seconds.
Isolators
Define the quantity of isolators installed per Z-loop, range
0-16.
AGV
Specifies whether the Alarm Group Verification (AGV)
function is enabled or disabled. Two modes are
provided:
Address group check:
When enabled, the panel
verifies that the correct device addresses exist between
loop isolators.
Partial short check:
When enabled, checks for partial
short circuits and data corruption, isolating the cause with
the loop isolators.
Time update
When this menu is [ENABLED], setting the time and date
in a panel which is part of a network of panels, causes
the time and date of all the panels in the network to be
updated.
Event time disp
Enabling this function causes the time of each alarm to
be displayed on the LCD display. This reduces the
number of characters allowed for the zone message to
31.
Flash healthy LED
With this function enabled, the LED's on sensors and line
devices flash once every 20 seconds to indicate that the
device is present and healthy. When a device is in
alarm, the LED flashes once every 2 seconds. With this
function disabled, the LED's remain off when the device
is normal.
Zone LED link
The zone LED's can be set to be automatically linked to
the system zones, or to be programmed to different
zones with I/O-mapping. This menu defines whether the
zone LED's are zone-linked or programmable.
Time set level
This function enables either free access to the "set time"
facility, or limits access to access level 2.
Smoke alert dly
The smoke alert delay is used to provide an initial local
alarm at a detector fitted with a sounder base, without
alerting the panel. This menu allows the time before the
panel is alarmed to be set between 1 - 5 minutes. This
function only operates with ZP732 "Duet" detectors. This
function is allocated to individual sensors in the
"Individual settings" menu.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......