ZP3 Fire Control Panel
System Commissioning
ZP3 Fire Control Panel Manual
Page 8 - 4
UD1160.8 Iss 6 (25/02/2005)
I
8
Z-loop functional tests
Connect all the loops to the panel. Power-up the panel, and allow the panel to go through
the self-diagnostics, device acceptance, and automatic calibration. Then go into the Setup|
Points|Accept Points menu, and manually accept all devices online. Then carry out the
following checks.
Identify the device addresses on each loop that are [1] the closest to the panel, [2] the
furthest from the panel (ie, near the end of the Z-loop), and [3] about halfway along the Z-
loop.
In the maintenance|reports to screen|point analogues menu, check that the first analogue
value (the "Reference Value", V1) of each device is within the range 208 - 216 counts, and
within 5 counts of each other.
If the Reference Value is substantially reducing between the beginning and the end of the Z-
loop, this is an indication that the wiring is out of specification, resulting in signal loss. This
could be caused by wiring that is inadequately sized, a loop that is too long, by loose
connections, or similar faults. If this is the case, the fault must be found and rectified.
Data wiring RS485
Check that RS485 data cabling connecting panels together meets the requirements of the
Ziton ZP Wiring Guide. As a guideline, this must be high-quality, screened, data cable, with
a maximum of 2000 metres of cable connected in any one network.
The cable terminating jumpers on the communications boards must be set correctly; see the
applicable equipment data sheets.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......