ZP3 Fire Control Panel
EN54 Setup Requirements
ZP3 Fire Control Panel Manual
UD1160.E Iss 6 (25/02/2005)
Page E - 1
I
E
Setup to conform to EN54: all paragraph numbers refer to EN54 part 2 of 1997 unless
otherwise notated.
1.
Para 7.1.4 & 8.1.3 - AVF shall be switched off for all points
2.
Para 7.3.1 - Under menu \setup\system configuration\zone LED link, zone LED's shall
be linked to the appropriate zones
3.
In menu \setup\system configuration\control keyswitch level
Para 7.4.1
The "accept" key shall be set up to level 1 or 2
Para 7.6.1
The "reset" key shall be set up to level 2
Para 7.8(a)
The "silence alarms" key shall be set up to level 2
Para 7.8(b)
The "sound alarms" key shall be set up to access level 2
4.
Para 7.8 - If accessory board ZP3AB-MA8 outputs are required to serve the function
of "output to fire alarm devices (item C)" then they must be defined as "sounder
outputs" when mapping. "Standard outputs" and use of non-monitored output boards
shall not be used to comply to EN54 item C requirements.
5.
Para 7.10 - If accessory board ZP3AB-MA8 outputs are required to serve the function
of "control to fire protection equipment" then they must be defined as "control outputs"
when mapping. The programming must not include delays to output when the output is
used to serve the function of "control to fire protection equipment." "Standard outputs"
and use of non-monitored input/output boards shall not be used to comply to EN54
item G requirements.
6.
Para 7.11(a) - Under menu \setup\system configuration\relays\sounder relays, the
sounder relays must be defined as "programmable". The relays must then be mapped
as outputs (addresses 09-173 and 09-178) using the I/O mapping function. They must
defined as "sounder outputs", silencing with no delay. (Note: a suitable input would be
the common fire LED at address 09-129).
7.
Para 7.11(c) - The day delay and more time extension shall be set to a maximum of
10 minutes as it automatically effects the delay to RMC alarm output.
8.
Para 7.11(c) - The I/O mapping to common sounder outputs (addresses 09-173 and
09-178) shall be set to a maximum delay of 10 minutes (including day delay and more
time extension if operating in day mode)
9.
Para 7.11(d) - Under menu \setup\system configuration\panel options\day delay
override set up so that callpoints do override the day delay.
10.
Para 7.12 - To meet co-incidence detection requirements either:
a) Use the coincidence function in the setup/zoning menu to inhibit the indication of
fire alarm condition (first alarm in will show as a pre-alarm)
or
b) Facilitate option to inhibit fire alarm devices and fire protection equipment by
mapping each appropriate output double knock from the zone.
11.
Para 8.2.4(c) - Earth fault monitoring shall be enabled (by inserting link J1 on the Main
Control Board)
12.
Para 8.2.5/6 The auxilliary 24 Volt power supply output shall not be used to drive
unmonitored equipment i.e. equipment which will not automatically notify a fault to the
control panel should loss of power occur. Line units such as ZP752-2 are monitored.
13.
Para 12.4.4 - All internal components of the panel enclosure shall be left inside the
enclosure to ensure EMC compatibility. The panel shall remain locked with key
removed during operation.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......