ZP3 Fire Control Panel
Maintenance
ZP3 Fire Control Panel Manual
Page 1 - 6
UD1160.M Iss 6 (25/02/2005)
I
M
1.2.3 Annual Service
The following is the schedule for the annual service that must be carried out on the system.
Annual Checks
•
Quarterly service
Repeat the quarterly service checks.
•
Input-Output configuration test
Using a fairly large representative sample, verify by testing that the input-output
mapping operates as programmed. Activate an input, such as a sensor, callpoint, or
interface unit, and verify that the correct outputs operate. Also check that the outputs
function correctly, for example, that they pulse, or operate continuously, that any
delays operate correctly, etc.
•
Building changes check
Visually check that the internal structural layout of the building, including inter-office
partitioning, has not changed from the system specification to such an extent that it
may affect the efficient operation of the fire alarm system.
•
Completion of Service
Restore the system to normal condition, re-enable any disabled devices, re-connect
any disconnected devices, re-connect all external systems that were disconnected for
the testing, and ensure that the system is left in 100% working condition. Advise all
staff and the remote manned centre that testing is complete, and that any alarm now
received must be treated as real.
Содержание ZP3
Страница 1: ...ZITON ZP3 Fire Control Panel Installation Operation Maintenance...
Страница 2: ......
Страница 10: ......
Страница 11: ...ZP3 Fire Control Panel Installation Manual Section 1 System Overview UD1160 1 Issue 6 25 02 2005...
Страница 12: ......
Страница 29: ...ZP3 Fire Control Panel Installation Manual Section 2 ZP3 Panel UD1160 2 Issue 6 25 02 2005...
Страница 30: ......
Страница 63: ...ZP3 Fire Control Panel Installation Manual Section 3 Power Supply UD1160 3 Issue 6 25 02 2005...
Страница 64: ......
Страница 81: ...ZP3 Fire Control Panel Installation Manual Section 4 Installation UD1160 4 Issue 6 25 02 2005...
Страница 82: ......
Страница 91: ...ZP3 Fire Control Panel Installation Manual Section 5 Field Wiring UD1160 5 Issue 6 25 02 2005...
Страница 92: ......
Страница 106: ......
Страница 107: ...ZP3 Fire Control Panel Installation Manual Section 6 Software Programming UD1160 6 Issue 6 25 02 2005...
Страница 108: ......
Страница 114: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual Page 6 6 UD1160 6 Iss 6 25 02 2005 I6...
Страница 115: ...ZP3 Fire Control Panel Software Programming ZP3 Fire Control Panel Manual UD1160 6 Iss 6 25 02 2005 Page 6 7 I6...
Страница 128: ......
Страница 129: ...ZP3 Fire Control Panel Installation Manual Section 7 System Configuration UD1160 7 Issue 6 25 02 2005...
Страница 130: ......
Страница 143: ...ZP3 Fire Control Panel Installation Manual Section 8 System Commissioning UD1160 8 Issue 6 25 02 2005...
Страница 144: ......
Страница 149: ...ZP3 Fire Control Panel Installation Manual Section 9 Peer to peer 3 Protocol UD1160 9 Issue 6 25 02 2005...
Страница 150: ......
Страница 158: ......
Страница 159: ...ZP3 Fire Control Panel Installation Manual Operator Instructions UD1160 O Issue 6 25 02 2005...
Страница 160: ......
Страница 189: ...ZP3 Fire Control Panel Installation Manual Maintenance UD1160 M Issue 6 25 02 2005...
Страница 190: ......
Страница 209: ...ZP3 Fire Control Panel Maintenance ZP3 Fire Control Panel Manual UD1160 M Iss 6 25 02 2005 Page 1 19 IM...
Страница 214: ......
Страница 215: ...ZP3 Fire Control Panel Installation Manual Appendix E EN54 Setup Requirements UD1160 E Issue 6 25 02 2005...
Страница 216: ......
Страница 219: ...ZP3 Fire Control Panel Installation Manual Appendix W ZP Wiring Guide UD1160 W Issue 6 25 02 2005...
Страница 220: ......