6.6.4 Inertia mode and related parameters
The adaptive default parameter is defined as small inertia mode. If the load inertia far exceeds the
allowable load inertia of the motor (such as 60 times inertia of the 60 motor), the adaptive large inertia
mode can be turned on.
Parameter
Meaning
Default
setting
Modification
Effective
P2-03
n.0□□□
Adaptive small inertia mode
n.0□□□
Servo bb
Re-power
on
n.1□□□
Adaptive large inertia mode
Parameter
Meaning
Default setting
Modification
Effective
P2-05
Adaptive speed loop gain
400
Note1
Servo bb
At once
P2-10
Adaptive speed loop integral
500
Servo bb
At once
P2-11
Adaptive position loop gain
100
Servo bb
At once
P2-07
Adaptive inertia ratio
0
Servo bb
At once
P2-08
Adaptive speed observer gain
60
Servo bb
At once
P2-12
Adaptive stable max inertia ratio
30
Servo bb
At once
P2-16
Adaptive motor rotor inertia coefficient
100
Servo bb
At once
P2-19
Adaptive bandwidth
50
Note2
Servo bb
At once
P6-05
Adaptive large inertia mode speed loop
gain
200
Servo bb
At once
P6-07
Adaptive large inertia mode inertia ratio
50
Servo bb
At once
P6-08
Adaptive large inertia mode speed
observer gain
40
Servo bb
At once
P6-12
Adaptive large inertia mode max inertia
ratio
50
Servo bb
At once
Note 1: DS5 series servo 750W and below driver default value is 400; other power section default
value is 200.
Note 2: DS5 series servo 400W and below driver default value is 70; other power section default value
is 50.
6.6.5 Recommended inertia ratio parameters
Under the adaptive default parameters, the load can only run steadily under a certain moment of inertia.
If the load inertia is large, some parameters need to be adjusted. The recommended parameters are as
follows (the parameters are modified under the default parameters).
Motor
flange
Inertia
Parameters
40~90
Within 20 times inertia
Adaptive small inertia mode (default parameters)
20-30 times inertia
Set P2-08=50, P2-12=40
30-40 times inertia
Set P2-08=50, P2-12=40, P2-07=10
40-50 times inertia
Set P2-08=50, P2-12=40, P2-07=30
50-80 times inertia
Switch to adaptive large inertia mode or set P2-08=40,
P2-12=50, P2-07=50
Note: The large inertia parameters can still drive a smaller inertia load. For example, when the
parameters of 50 times inertia are used in the mechanism of 20 times inertia, only the response will
become worse.
Содержание DS5L1 Series
Страница 1: ...DS5L1 series servo driver User manual WUXI XINJE ELECTRIC CO LTD Data No SC5 05 20200929 1 0 ...
Страница 2: ......
Страница 6: ......
Страница 33: ...Voltage DC 30V maximum Current SO1 DC 500mA maximum 400W and below servo can support SO others DC 50mA maximum ...
Страница 100: ...3 Set the auto tuning interface 4 Click ok to start inertia identification ...
Страница 106: ...3 set the auto tuning interface ...
Страница 112: ...with higher rigidity 6 Start auto tune 7 Open the servo enable then click ok ...
Страница 169: ...Appendix 9 Torque speed characteristic curve ...
Страница 170: ......