Installation and Connection
46 | CTW900
Connector XC1
Factory Default Function
Specifications
1
+REF
Positive reference for
potentiometer
Output voltage: +5.4 V, ±5 %
Maximum output current: 2 mA
2
AI1+
Analog Input 1: Speed
reference (remote)
Differential analog input
Resolution: 12 bits
Signal: 0 to +10 V (R
IN
= 400 k
)
0 to 20 mA / 4 to 20 mA (R
IN
= 500
)
Maximum voltage: ±30 V
3
AI1-
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %
Maximum output current: 2 mA
5
AI2+
Analog Input 2: Speed
reference (remote)
Differential analog input
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
IN
= 400 k
)
0 to 20 mA / 4 to 20 mA (R
IN
= 500
)
Maximum voltage: ±30 V
6
AI2-
7
AO1
Analog output 1:
Effective Speed
Analog output with galvanic isolation
Resolution: 11 bits
Signal: 0 to +10 V (R
L
10 k
)
0 to 20mA / 4 to 20 mA (R
L
500
)
Protected against short circuit
8
AGND
(24V)
Reference 0 V for the analog
outputs
Connected to ground (frame) via impedance:
Resistor of 940 k
in parallel with capacitor of 22 nF
9
AO2
Analog output 2:
Armature Current
Analog output with galvanic isolation
Resolution: 11 bits
Signal: 0 to +10 V (R
L
10 k
)
0 to 20 mA / 4 to 20 mA (R
L
500
)
Protected against short circuit
10
AGND
(24 V)
Reference 0V for the analog
outputs
Connected to ground (frame) via impedance:
Resistor of 940 k
in parallel with capacitor of 22 nF
11
DGND
Reference 0V of the 24 Vdc
power supply
Connected to ground (frame) via inductor of 100 µH
(impedance 1.6
)
12
COM
Common point of the digital
inputs
13
24 Vdc
24Vdc Power supply
24 Vdc Power supply, ±8 %
Capacity: 500mA
14
COM
Common point of the digital
inputs
15
DI1
Digital input 1:
General Enable
6 Isolated digital inputs
High level:
18 V
Low level:
3 V
Maximum input voltage: 30 V
Input current: 11 mA @ 24 Vdc
16
DI2
Digital input 2:
Run/Stop
17
DI3
Digital input 3:
Not Used
18
DI4
Digital input 4:
Not Used
19
DI5
Digital input 5:
JOG (remote)
20
DI6
Digital input 6:
2nd Ramp
21
NF1
Digital output 1 DO1 (RL1):
No Fault
Maximum voltage of the contacts: 240 Vac
Maximum current: 1 A
NC: normally closed contact
C: common
NO: normally open contact
22
C1
23
NA1
24
NF2
Digital output 2 DO2 (RL2):
N > N
x
25
C2
26
NA2
27
NF3
Digital output 3 DO3 (RL3):
N* > N
x
28
C3
29
NA3
Figure 5.9
– Signals of connector XC1 and connection of the digital inputs as active high
NOTE!
In order to use the digital inputs as active low, it is necessary to remove the jumper between XC1:
11 and 12 and change it to XC1: 12 and 13.
As default, the analog inputs and outputs come from the factory selected for the range 0 to +10V.
In order to change its operation range, you can change the position of switch S1, located on the upper left
corner of the CC900 electronic board.