Detailed Description of the Parameters
.
CTW900 | 109
Description:
When a fault occurs (except for F074, F084, F099 and F149), the CTW900 may automatically reset after the
time set in P0340 has elapsed.
After the auto-reset, if the same fault occurs again for three times consecutively, the auto-reset function will be
disabled. A fault is considered consecutive if it happens again within 30 seconds after the auto-reset.
Therefore, if a fault occurs four times consecutively, the converter will remain disabled and the fault will continue
being displayed until the CTW900 is re-energized.
Note:
■
If P0340
2s, the auto-reset function will be disabled.
NOTE!
Faults F051 and F156 allow the conditional reset, that is, the automatic reset will only occur if the
temperature returns to the normal operating range.
P0348 – Configuration of the Overload Protection
Adjustable Range:
0 = Inactive
Factory Setting:
1
1 = Fault/ Alarm
2 = Fault
3 = Alarm
Properties:
CFG1
Groups of
01 PARAMETER GROUPS
Access via HMI:
38 Protections
........
Description:
This parameter allows configuring the desired form of actuation for the motor overload protection (Ixt).
Check the table below with the details of the actions of each of the available options.
Table 7.20
– Actions for the options of parameter P0348
P0348
Action
0 = Inactive
The overload protection is disabled. Neither faults, nor alarms will be
generated for the motor operation in the overload condition.
1 = Fault/ Alarm
The converter will display an alarm (A046) when the motor reaches the level
set in P0349, and it will generate a fault (F072) when the motor reaches the
actuation value of the overload protection. Once the fault is generated, the
converter is disabled.
2 = Fault
When the motor reaches the actuation level of the overload protection, fault
F072 will be generated and the converter will be disabled.
3 = Alarm
The alarm will be generated (A046) only when the motor reaches the value
set in P0349, and the converter will continue operating.
P0349 – Overload Alarm Level
Adjustable Range:
70 to 100 %
Factory Setting:
85 %
Properties:
CFG1
Groups of
01 PARAMETER GROUPS
Access via HMI:
38 Protections
........
Description:
This parameter defines the level for alarm actuation of the motor overload protection (A0046), and it is
expressed in percentage of the overload integrator limit value.
It will only be effective when P0348 is set to 1 (Fault/Alarm) or to 3 (Alarm).