Detailed Description of the Parameters
.
110 | CTW900
P0350 – Configuration of the Ia > Ix Detector
Adjustable Range:
0 = Active
Factory Setting:
0
1 = Inactive during the acceleration or braking
Properties:
CFG1
Groups of
01 PARAMETER GROUPS
Access via HMI
:
38 Protections
........
Description:
It allows deactivating the Ia > Ix function of the digital inputs during accelerations or braking.
P0352 – Configuration of the Protection against Tacho/ Encoder Loss
Adjustable Range:
0 = Active
Factory Setting:
0
1 = Inactive
Properties:
CFG1
Groups of
01 PARAMETER GROUPS
Access via HMI:
38 Protections
........
Description:
It allows deactivating the protection against Tachogenerator or Encoder Loss.
It will be only effective when P0202 is set to 1 (Tacho DC) or 2 (Encoder).
DANGER!
By setting P0352 = 1, the protection against Tacho/Encoder loss will be inactive, and the motor
can accelerate up to the maximum speed in case the speed feedback signal is disconnected or is
interrupted.
P0353 – EMF Level for the Protection against Tacho/ Encoder Loss
Adjustable Range
: 0 to 1000 V
Factory Setting:
50 V
P0354 – Speed Difference for the Protection against Tacho/ Encoder Loss
Adjustable Range:
0 to 100 %
Factory Setting:
25 %
Properties:
CFG1
Groups of
01 PARAMETER GROUPS
Access via HMI:
38 Protections
........
Description:
These parameters define the actuation level of the protection against Tacho/Encoder loss (F154).
The value of P0353 specifies the EMF voltage from which the protection against Tacho/ Encoder loss will be
enabled to actuate, while the value of P0354 determines the maximum acceptable difference between the EMF
and the speed feedback signal.
Example: For the default factory settings and a motor of rated voltage of 460 V (P0400), the application of the
command ‘Run’ without the feedback signal connected will make the protection F154 actuate when
the EMF value reaches 115 V, meeting the conditions of P0353 (> 50 V) and of P0354 (|P0002 –
P0041|> 25 %).
Figure 7.17
– Monitoring area of the protection against Tacho/ Encoder Loss according to the value in P0353