Detailed Description of the Parameters
.
104 | CTW900
Table 7.19
– Example of the first characters of the code P0028 for PROFIBUS DP-05 and FLASH memory module
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
0
1
0
0
0
0
5
0
P0295 – Drive Rated Current
Adjustable Range:
0 = 20 A
Factory Setting:
1 = 50 A
2 = 90 A
3 = 125 A
4 = 180 A
5 = 260 A
6 = 480 A
7 = 640 A
8 = 1000 A
9 = 1500 A
10 = 2000 A
11 = 1320 A (Rack)
12 = 1700 A (Rack)
13 = 1900 A (Rack)
14 = 2000 A (Rack)
15 = 2120 A (Rack)
16 = 3000 A (Rack)
17 = 3125 A (Rack)
18 = 3200 A (Rack)
19 = 1000 A (Rack)
Properties:
RO
Groups of
01 PARAMETER GROUPS
Access via HMI:
36 Drive Data
........
Description:
Read only parameter that defines the converter rated current (factory preset).
NOTE!
In cases of replacement of the control board, it is possible to change the value of the parameter
P0295 manually, adjusting it to the rated current indicated on the product label.
For that, it is necessary to program the parameter 0000 with the special password 1734.
P0296 – Line Rated Voltage
Adjustable Range:
0 = 200-240 V
Factory Setting:
0
1 = 380 V
2 = 400-415 V
3 = 440-460 V
4 = 480 V
5 = 500-525 V
6 = 550-575 V
7 = 600 V
8 = 660-690 V
9 = 740-990 V
Properties:
CFG2
Groups of
01 PARAMETER GROUPS
Access via HMI:
36 Drive Data
........
Description:
It defines the converter power supply, and it must be set according to the power supply to which the CTW900
is connected.