Installation and Connection
CTW900 | 41
Table 5.1
– Recommended Wiring for Power and Grounding Connection, as per NBR 5410
Armature Input
Connection (R/S/T)
Armature Output
Connection (A1/B2)
Model
CTW900
Cables
[mm
2
]
Busbars
[mm x mm]
Cables
[mm
2
]
Busbars
[mm x mm]
Field
Wiring
[mm
2
]
Grounding Wiring
(PE)
[mm
2
]
20A
4
12 x 2
4
12 x 2
1.0
4
50A
10
12 x 2
10
12 x 2
1.0
10
90A
25
12 x 2
25
12 x 2
1.0
16
125A
35
12 x 2
35
12 x 2
1.0
16
180A
70
20 x 3
70
20 x 3
2.5
35
260A
95
20 x 3
95
20 x 3
2.5
50
480A
2 x 95
30 x 5
2 x 120
30 x 10
4.0
95
640A
2 x 150
30 x 5
3 x 120
30 x 10
4.0
150
1000A
3 x 185
30 x 10
4 x 150
40 x 10
4.0
185
1500A
4 x 240
80 x 10
5 x 185
80 x 10
4.0
2 x 240
2000A
5 x 240
100 x 10
6 x 240
100 x 10
4.0
2 x 240
NOTE!
The values of Table 5.1 are only valid in the following conditions:
■
copper cables with PVC 70°C insulation or
■
silver or bare copper busbars and with rounded edges of 1-mm radius;
■
maximum ambient temperature of 40°C;
■
installation in vertical or horizontal perforated channels;
■
arrangement of the cables in a single layer.
For installation in other conditions, refer to NBR 5410.
NOTE!
The converter output wiring (A1/B2) must be installed separately from the line input wiring (R/S/T),
as well as from the control and signal wiring.
5.3.4
Protection Fuses
In order to protect the product against short circuit, ultra fast fuses must be used at the converter input,
dimensioned according to the current and to the maximum of the power I
2
t semiconductors.
For Antiparallel converters (4-Q), it is also necessary to install fuses at the converter output (A1/B2), as shown in
Figure 5.6.
Figure 5.6
– Configuration of the elements for the protection of the armature circuit of the CTW900
CTW900
U
nidirectional
(1-Q)
M
CTW900
A
ntiparallel
(4-Q)
M
fuses
fuses
fuses
R S T
R S T
A1
B2
A1
B2
Содержание CTW900
Страница 2: ......
Страница 52: ...Installation and Connection 52 CTW900 Figure 5 16 Connections in XC1 for configuration 4...
Страница 69: ...Detailed Description of the Parameters CTW900 69 Figure 7 3 Block diagram of the speed reference...
Страница 135: ...Detailed Description of the Parameters CTW900 135 Figure 7 21 Block diagram of the control of the CTW900...