Detailed Description of the Parameters
.
70 | CTW900
7.3.4
Limits [23]
The parameters of this group function as the motor speed or current limiters.
P0133 – Minimum Speed
Adjustable Range:
0 to 10000 rpm
Factory Setting:
0 rpm
Properties:
Groups of
01 PARAMETER GROUPS or 04 BASIC APPLICATION
Access via HMI:
23 Limits
........
P0134 – Maximum Speed
Adjustable Range:
0 to 10000 rpm
Factory Setting:
1800 rpm
Properties:
Groups of
01 PARAMETER GROUPS
Access via HMI:
23 Limits
........
Description:
They define the maximum/minimum limit values of the motor speed reference when the converter is enabled,
and are valid for any kind of reference signal.
Figure 7.4
– Actuation of the limits P0133 and P0134 in the speed reference
P0136 – Current Limit for Maximum Speed
Adjustable Range:
2 to 125 %
Factory Setting:
125 %
Properties:
P0138 – Speed Limit for Maximum Current
Adjustable Range:
0 to 10000 rpm
Factory Setting:
1800 rpm
Properties:
Groups of
01 PARAMETER GROUPS or 01 PARAMETER GROUPS
Access via HMI:
23 Limits
........
38 Protections
........
Description:
These parameters allow decreasing the current limitation value for speeds above the specification in P0138,
according to the curve of Figure 7.5:
Figure 7.5
– Current limitation considering the speed