Detailed Description of the Parameters
.
62 | CTW900
RO:
Read only parameter;
CFG1
: Configuration parameter level 1: change not allowed with the converter Running;
CFG2
: Configuration parameter level 2: change only allowed with the converter Disabled.
7.3
PARAMETER GROUPS [01]
7.3.1
HMI [20]
In the “20 HMI” group are the parameters related to the presentation of information on the keypad (HMI) display.
See detailed description below of the possible settings of those parameters.
P0193 – Day of the Week
Adjustable Range:
0 = Sunday
Factory Setting:
0
1 =
Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
P0194 – Day
Adjustable Range:
01 to 31
Factory Setting:
01
P0195 – Month
Adjustable Range:
01 to 12
Factory Setting:
01
P0196 – Year
Adjustable Range:
2000 to 2099
Factory Setting:
2012
P0197 – Hour
Adjustable Range:
00 to 23
Factory Setting:
00
P0198 – Minutes
Adjustable Range:
00 to 59
Factory Setting:
00
P0199 – Seconds
Adjustable Range:
00 to 59
Factory Setting:
00
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
20 HMI
Description:
These parameters set the date and time of the real time clock of the CTW900. It is important to set them with
the correct date and time so that the fault and alarm log occurs with real date and time information.
P0200 – Password
Adjustable Range:
0 = Inactive
Factory Setting:
1
1 = Active
2 = Change Password
Properties:
Groups of
01 PARAMETER GROUPS
...
Access via HMI:
20 HMI
Description:
It allows changing the password status, configuring it as active or inactive, and also setting its value. The table
below describes the details of each option.